Interruptor de rotura de carga de alto voltaje de interior 24kV 12/24kV
Información básica
Modelo: FN12
Descripción del producto
1 ISO9001: 2000
2 24 kV 50 HZ
3 Safty, perfecto, pérdida energía pérdida
interior carga rotura interruptor de alto voltaje 24kV
uso condition
a.ambient temperatura - 25 º c- + 40oC
b.elevation≤1000m
c.humidity:daily humidity≤95%,monthly≤90%
promedio d. terremoto supere grado 8
e.no fuego, explsion, errosion químico...
f.pollution:level 2
principal técnica parámetros
Item |
Unit |
Parameter |
|
Rated Voltage |
[kV] |
24 |
|
Power Frequency Withstand voltage 50Hz/1min |
To earth and between phases |
[kV] |
70 |
Across isolation (contacts open) |
80 |
||
Impulse Withstand Voltage |
To earth and between phases |
[kV] |
170 |
Across isolation (contacts open) |
190 |
||
Impulse withstand voltage to earth and between phases |
Up[kV] |
125 |
|
Rated current |
In[A] |
400-630 |
|
Breaking capacity of active circuits (cos ø 0.7) and ring circuits at 0.3 Vn |
Isc[kA] |
400-630 |
|
Breaking capacity of no-load transformers |
Isc[kA] |
25 |
|
Breaking capacity of no-load lines / cables |
Isc[kA] |
25 |
|
Earth fault breaking capacity |
Isc[kA] |
200 |
|
Cable and line-charging breaking current under earth fault condition |
Isc[kA] |
50 |
|
Transfer current |
In[A] |
800 |
|
Short time withstand current - 1 sec. |
Ik[kA] |
12,5-25 |
|
Short time withstand current - 3 sec. |
Ik[kA] |
12,5-20 |
|
Making capacity |
[kA] |
31,5-62,5 |
Grupos de Producto : Disyuntores e interruptores > Interruptor de rotura de carga